Skip to content
Gridcensus

Battle Mountain

Brownfield

Lander, Nevada · WECC

DC Readiness
53.7
Fair / 100

Battle Mountain is a brownfield datacenter candidate site in Lander, Nevada, interconnecting through WECC. It screens at 53.7/100 DC Readiness with a catalogued 8 MW of candidate capacity and a 5.8 yrs average interconnection-queue wait.

Power & interconnection

Nearest substationBATTLE MOUNTAIN
Substation distance2.3 mi
Substation voltage120 kV
Available capacity8 MW
Utility commercial rate0.06¢/kWh
UtilitySIERRA PACIFIC POWER COinvestor ownedfavorable to large load · terms ≥ 100 MWClean Transition Tariff (large loads)

Speed to power

Interconnection outlookConstrained
≈ 5.8 yrs typical interconnection wait

Deep queue and long historical waits — plan for a multi-year interconnection timeline and engage the utility early.

ISO / RTO regionWECC
Queue depth53
Avg queue wait5.8 yrs
Recent queue wait5.8 yrs
Completion rate10%
Withdrawal rate90%

Connectivity

Fiber providers1
Fiber coverage35.5%
Nearest cloud providerGCP
Nearest cloud regionus-west3
Cloud region distance263.2 mi

Site characteristics

Site typeBrownfield
Land contactState Environmental Cleanup Program
Land owner typeprivate
Buildability75.0/100
Former useoil
Existing capacity8 MW
Retirement date2011-01-01

Risk & environment

Environmental constraintLow (30/100)
Flood zoneZone X
Water stress (WRI)4.50
Wetlands (NWI)Clear
Critical habitatClear
Superfund nearbyPresent
Superfund siteATLAS TOWING SERVICE INC
Hazard sub-score78/100
Construction cost index117.5 (avg 100)

Location context

Nearest datacenterTesla Gigafactory
DC distance153.4 mi
Nearest rail0.2 mi
Nearest gas pipeline6.2 mi
Nearest fiber route177.4 mi
County hazard (FEMA NRI)Very Low (12)
DC tax incentiveYes (sales_tax_abatement)
Commercial electricity5.83¢/kWh
Industrial electricity5.01¢/kWh
Cooling degree days2,000
Heating degree days3,700
Land price / acre$1,115

Regulatory climate

Moderatestate posture · as of 2026-08

No notable statewide DC restriction on record; confirm local zoning and utility tariffs.

DC tax incentiveNo / suspended

Incentive detail: Partial abatement of sales/use tax and personal property tax for $25M+ DC investments.

Site location

◆ Loading map…
≥ 7560–7540–60≤ 40
This site + 8 nearby

Get alerts

Track Battle Mountain

Get an email when its DC-readiness score, available capacity, or interconnection-queue status changes.

No spam. Just the alerts you asked for.

Full DC Readiness breakdown

All 13 weighted sub-scores (0–100) behind the composite DC Readiness score.

Power availability20%
30
Speed to power20%
48
Fiber connectivity12%
61
Energy cost10%
95
Water risk7%
28
Natural hazard6%
78
Buildability7%
75
Labor market4%
50
DC cluster4%
20
Land / acreage3%
78
Construction cost3%
52
Gas pipeline2%
80
Tax incentive1%
100
Climate / cooling1%
25

Nearby comparable sites

Other scored datacenter candidate sites in Lander, ranked by DC Readiness.

Sites near Battle Mountain
SiteTypeVoltageCapacityQueue waitScore
FRONTIERSubstation-Adjacent230 kV300 MW6.9 yrs56.0
AUSTINSubstation-Adjacent230 kV300 MW6.9 yrs55.0
EC Near Battle MountainGreenfield——5.8 yrs54.6
EC Near Battle MountainGreenfield——5.8 yrs54.4
EC Near Battle MountainGreenfield——5.8 yrs54.3
EC Near Battle MountainGreenfield——5.8 yrs54.0
EC Near Battle MountainGreenfield——5.8 yrs52.6
BATTLE MOUNTAINSubstation-Adjacent120 kV100 MW6.9 yrs52.4

Dataset updated . Screening estimates derived from public data sources.

Figures are screening estimates derived from public infrastructure data. Catalogued capacity reflects theoretical candidate capacity, not deliverable or committed interconnection. Confirm all values with the utility, ISO, and on-the-ground due diligence.

Go deeper than the public screen